Step 11: Zs and the maximum Zs

In an earth fault, the current doesn't just go round your 27 m of cable. It goes all the way back to the star point. So we add the external part, Ze.

Supply transformer star point CU B32 MET R1: line conductor (16 mm²) Cooker metal case fault to case R2: CPC (6 mm²) Ze (outside the installation) supply line (part of Ze) Zs = Ze + (R1 + R2) = 0.26 + 0.137 = 0.397 Ω
The earth fault loop. Ze (0.26 Ω, measured, given in the brief) covers everything outside the installation. R1 + R2 is the circuit you're designing.

Working

Zs = Ze + (R1 + R2)
   = 0.26 + 0.137
   = 0.397 Ω

Table 41.3: max tabulated Zs, 32 A Type B = 1.37 Ω
0.397 Ω ≤ 1.37 Ω ✓  → automatic disconnection of supply will happen

BS 7671 · Chapter 41 · Table 41.3 · max Zs for circuit-breakers (32 A Type B = 1.37 Ω) · p.75

Tabulated (BS 7671) vs measured (OSG / GN3)

  • Why not the OSG's 1.09 Ω? Because this is design. You want to know the circuit disconnects when it's working, at its full operating temperature (70 °C). BS 7671's values are for that.
  • The On-Site Guide Table B6 (and GN3) give maximum measured values. They're about 80% of the tabulated ones, for an inspector testing a cold circuit (around 20 °C). For example, a new circuit is tested on a mild April day. The 20% margin allows for the cable warming up in use.
  • Compare them: 32 A Type B is 1.37 Ω in BS 7671 and 1.09 Ω in the OSG (Table B6). 6 A Type B is 7.28 Ω in BS 7671, and 80% of that is about 5.82 Ω. Check your copy.

On-Site Guide · Table B6 · max measured Zs (≈ 80% of Table 41.3)

Step 12: disconnection time (Table 41.1)

See Reg 411.3.2.2. Table 41.1 is for final circuits. Two kinds of circuit fall outside it and are allowed longer:

  • distribution circuits (feeding another board, e.g. a garage, shed or another building), and
  • final circuits above 32 A feeding only fixed equipment, or above 63 A with socket-outlets.

Those get 5 s on TN (or 1 s on TT). Our circuit is a 32 A final circuit with a socket, so we use Table 41.1.

  • Choose the voltage band from U0, the voltage to earth: over 120 V up to 230 V. That's the most commonly used column. Even on three-phase, U0 is still 230 V, so don't jump to the 400 V column.
  • AC, TN system → 0.4 s maximum.
The shortcut
If the actual Zs is below the maximum tabulated Zs, the device will disconnect in time. That's what the Table 41.3 values are built from.

BS 7671 · Reg 411.3.2.2 and Table 41.1 · maximum disconnection times · p.71 (table at the top of p.72)

Test yourself on it

The tests are in the members’ area. Get one wrong and it shows you why, and where to revise.

Get access

Get new notes and exam tips from Sparky

About one email a fortnight. Unsubscribe any time. Privacy notice

That was one section. There are 583.

Sparky Study Notes is the whole Level 3 syllabus written up like this: the explanation, the worked example, and where it is in your book. With a video lesson for every part and a practice paper for every exam.

  • 583sections of written notes
  • 35video lessons
  • 1,463practice questions
  • 146diagrams, redrawn
  • 18th Edition
  • Building Regs
  • PAT
  • Fundamental Inspection & Testing
  • Initial Verification
  • Periodic Inspection & Testing
Get access — £100 12 months. One payment. See what’s inside