Cable calculation, steps 1 and 2: cable type and installation methodWhich reference method is cable in trunking?

Free from the notes: Sparky’s video on it, the section word for word as members see it, and a PDF to keep.

From Sparky’s full video lesson. Members get the whole lesson on every notes page.

The question at the end: Which reference method is cable in trunking? The answer is in the notes below.

The notes

Exactly as they are on the site.

Download these notesPDF · free to keep

Step 1: cable type (Table 4A1)

In a dwelling we'll use twin and earth. It's the most versatile cable on the market. T&E isn't "domestic only". You can use it in commercial and industrial work too, and you can use singles or flex in a house. Chapter 52 covers the do's and don'ts of wiring systems.

The route: use the existing trunking (there's room, and the client is happy with it). That means less lifting floorboards, chasing walls or going through ceilings. Above the cooker position, the cable comes out of the back of the trunking into a chase straight down.

Table 4A1 tells you whether each cable type is permitted (P) or not permitted (NP) with each installation method.

  • Non-sheathed cables (singles: a conductor with one layer of coloured insulation) are NP clipped direct or on cable tray, but permitted in conduit, trunking and ducting and on insulators.
  • Sheathed cables are split into multicore and single-core. A single-core sheathed cable is like a meter tail. T&E is multicore: line, neutral and CPC in one sheath.
  • Multicore sheathed cable is permitted almost everywhere, including in trunking. Clipped inside the chase counts as clipped direct, which is also permitted.

70 °C or 90 °C? 70 °C thermoplastic (PVC) is fine in a house. Think about 90 °C thermosetting or other cables where there's an increased risk of fire, a combustible building, or flammable materials stored or processed.

Our statement

70 °C thermoplastic twin and earth cable.
Table 4A1 suggests this cable type is suitable for trunking,
and clipped inside the chase.

BS 7671 · Appendix 4 · Table 4A1 · cable types vs installation methods (P / NP) · p.460 BS 7671 · Chapter 52 · selection and erection of wiring systems

Step 2: installation method (Table 4A2)

  • In the trunking: a multicore cable in trunking on a wooden or masonry wall (run horizontally or vertically) is Reference Method B.
  • In the chase: we assume the wall is thermally insulating. A multicore cable in a thermally insulating wall is Reference Method A (at the top of Table 4A2).
Always design to the worst case
When a cable passes through more than one installation method, note them all. Later, when you pick the cable size, use whichever method gives the lowest current rating.

If the wall isn't thermally insulating, stick with Method B throughout. The books give little guidance for this case, and it depends on the age of the house.

Our statement

Installation method:
  Ref Method B  (whilst in trunking)
  Ref Method A  (whilst in chase)

BS 7671 · Appendix 4 · Table 4A2 · installation methods · p.461

Test yourself on it

The tests are in the members’ area. Get one wrong and it shows you why, and where to revise.

Get access

Get new notes and exam tips from Sparky

About one email a fortnight. Unsubscribe any time. Privacy notice

That was one section. There are 583.

Sparky Study Notes is the whole Level 3 syllabus written up like this: the explanation, the worked example, and where it is in your book. With a video lesson for every part and a practice paper for every exam.

  • 583sections of written notes
  • 35video lessons
  • 1,463practice questions
  • 146diagrams, redrawn
  • 18th Edition
  • Building Regs
  • PAT
  • Fundamental Inspection & Testing
  • Initial Verification
  • Periodic Inspection & Testing
Get access — £100 12 months. One payment. See what’s inside