Regulation 433.1.1 is a long regulation that boils down to two conditions:

Ib ≤ In ≤ Iz   and   I2 ≤ 1.45 × Iz
(Iz is the cable's rating after the factors, see section 11)

I2 is the current that causes the protective device to actually operate (Reg 433.1.1(c)). A circuit-breaker marked 32 A doesn't trip at 32.1 A, 33 A, 35 A, 40 A or even 42 A. For a circuit-breaker, I2 = 1.45 × In.

Working

Iz        = 57 × 0.94 × 0.7      = 37.5 A
1.45 × Iz = 1.45 × 37.5         = 54.4 A
I2        = 1.45 × In = 1.45 × 32 = 46.4 A

24.5 ≤ 32 ≤ 37.5 ✓
46.4 A ≤ 54.4 A ✓   → Section 433 met: the cable won't overheat
020406080 Ib24.5 A In32 A Iz37.5 A I2 = 1.45 × In46.4 A 1.45 × Iz54.4 A Ib ≤ In ≤ Iz · I2 must not pass 1.45 × Iz
The design line for the cooker circuit (after diversity). Iz is the 57 A table value after the factors.
The rubber band
Cut a rubber band so it's a strip. Pull it until it just stops sagging: that's In. Stretch it to 1.45 times that length and leave it: eventually it snaps. That's I2, the device tripping on a sustained overload after a long time. Yank it hard and it snaps instantly: that's Ia, the instantaneous trip (step 13).

Why the slack? Diversity. If the tenants do all cook at once (three pans of pasta on full and a pizza in the oven), the circuit can draw more than the 24.5 A you designed for. I2 gives the device room to "stretch" over that period without tripping, while the cable (sized for this) stays safe.

Watch out: two details
1) A common mix-up is that I2 trips "after 10,000 seconds, about two hours". 10,000 s is just the top of the time axis on the Appendix 3 graphs (and it's nearer 2¾ hours). For circuit-breakers up to 63 A, the standard conventional time for I2 is 1 hour.
2) Iz is the cable's rating after the factors (37.5 A), not the 57 A table figure. 1.45 × 57 = 82.65 A would flatter the check; 1.45 × 37.5 = 54.4 A is the real limit, and I2 46.4 A is still inside it. For circuit-breakers and RCBOs, I2 = 1.45 × In, so once In ≤ Iz, the I2 check is automatically met.

BS 7671 · Reg 433.1.1 · overload: Ib ≤ In ≤ Iz and I2 ≤ 1.45 Iz (433.1.1(c)) · p.103

Test yourself on it

The tests are in the members’ area. Get one wrong and it shows you why, and where to revise.

Get access

Get new notes and exam tips from Sparky

About one email a fortnight. Unsubscribe any time. Privacy notice

That was one section. There are 583.

Sparky Study Notes is the whole Level 3 syllabus written up like this: the explanation, the worked example, and where it is in your book. With a video lesson for every part and a practice paper for every exam.

  • 583sections of written notes
  • 35video lessons
  • 1,463practice questions
  • 146diagrams, redrawn
  • 18th Edition