Cable calculation, step 8: voltage dropDoes it pass the 5 % limit?
Free from the notes: Sparky’s video on it, the section word for word as members see it, and a PDF to keep.
The notes
Exactly as they are on the site.
You get the mV/A/m from the same table as the current rating. For T&E, Table 4D5 has both. For some other cable types they're split: e.g. single-core 70 °C cable uses Table 4D1A for current ratings and Table 4D1B for mV/A/m.
÷ 1000 turns millivolts into volts. (A ring final divides by 4000.)
Working
16 mm² T&E → 2.8 mV/A/m (Table 4D5, mV/A/m column) VD = (2.8 × 24.5 × 27) ÷ 1000 = 1.85 V (≈ 1.8 V) Max for a non-lighting circuit = 5% of 230 V = 11.5 V 1.85 V ≤ 11.5 V ✓
- The low voltage drop is helped massively by the big cable. A smaller cable has more resistance, so more drop.
- Lighting circuits: 3% (6.9 V). Everything else: 5% (11.5 V).
- Three-phase: work from 400 V, so 5% allows 20 V.
BS 7671 · Appendix 4 · Table 4Ab · voltage drop limits 3% / 5%
Free section from Sparky Study Notes. The full Level 3 notes, 1,463 practice questions and the video lessons: sparkystudynotes.co.uk
Test yourself on it
The tests are in the members’ area. Get one wrong and it shows you why, and where to revise.
Get new notes and exam tips from Sparky
About one email a fortnight. Unsubscribe any time. Privacy noticeThat was one section. There are 583.
Sparky Study Notes is the whole Level 3 syllabus written up like this: the explanation, the worked example, and where it is in your book. With a video lesson for every part and a practice paper for every exam.
- 583sections of written notes
- 35video lessons
- 1,463practice questions
- 146diagrams, redrawn
- 18th Edition
- Building Regs
- PAT
- Fundamental Inspection & Testing
- Initial Verification
- Periodic Inspection & Testing