Cable calculation, step 4: diversityDoes a cooker really draw 41.7 amps?
Free from the notes: Sparky’s video on it, the section word for word as members see it, and a PDF to keep.
The notes
Exactly as they are on the site.
41.7 A assumes everything is on full at once, and nobody cooks like that. You turn the hob down once the pan boils. The oven sits at 180–220 °C, not flat out. And thermostats in the oven and hob keep clicking the elements off and on. So we can apply diversity.
You don't have to apply it. It's common-sense guidance, found only in the On-Site Guide (a guide). It's worth reading OSG Appendix A: maximum demand and diversity is a very subjective area.
On-Site Guide · Appendix A · maximum demand and diversity · p.149 On-Site Guide · Table A1 · current demand to be assumed (incl. household cooking appliances) · p.150 On-Site Guide · Table A2 · diversity by type of premises · pp.151–152 Cooking appliances row, "individual household" column
Table A2's wording is famously clumsy: 10 A + 30% of the full load of connected cooking appliances in excess of 10 A + 5 A if a socket-outlet is incorporated in the control unit. Table A1 says it more clearly: the first 10 A, plus 30% of the rest, plus 5 A for a socket. (Lighting is easier: 66% in a household. Cookers are the most complicated diversity sum.)
Working: Ib after diversity
Ib (full load) = 41.7 A 1) Take off the first 10 A: 41.7 − 10 = 31.7 A 2) 30% of the remainder: 31.7 × 0.3 = 9.51 A 3) Put the 10 A back: 9.51 + 10 = 19.51 A 4) Add 5 A for the socket: 19.51 + 5 = 24.51 A New Ib (after diversity) = 24.5 A (almost half!)
A smaller Ib saves time, effort and money: smaller cable is cheaper and easier to work with. But it's still your judgement. In an HMO, several tenants might cook at once. A family of five with a keen cake baker might have the oven on all day. Speak to the client. You could work it out with and without diversity and go somewhere in the middle. We work it both ways so you can see the difference (see section 14).
Keep the number the calculator gives. Rounding 24.5 A up to 25 A, for example, could tip you into a bigger cable than you need. (The working above starts from 41.7 A; the full 41.74 A gives 24.52 A, the same 24.5 A.)
Free section from Sparky Study Notes. The full Level 3 notes, 1,463 practice questions and the video lessons: sparkystudynotes.co.uk
Test yourself on it
The tests are in the members’ area. Get one wrong and it shows you why, and where to revise.
Get new notes and exam tips from Sparky
About one email a fortnight. Unsubscribe any time. Privacy noticeThat was one section. There are 583.
Sparky Study Notes is the whole Level 3 syllabus written up like this: the explanation, the worked example, and where it is in your book. With a video lesson for every part and a practice paper for every exam.
- 583sections of written notes
- 35video lessons
- 1,463practice questions
- 146diagrams, redrawn
- 18th Edition
- Building Regs
- PAT
- Fundamental Inspection & Testing
- Initial Verification
- Periodic Inspection & Testing