Prospective earth fault current (PEFC)

How many amps flow in the CPC during an earth fault? That's just Ohm's law, with one extra factor.

PEFC = (U0 × Cmin) ÷ Zs
Cmin = 0.95 for UK public LV supplies (Reg 411.4.4 Note 1)

Cmin is the minimum voltage factor. It allows for the supply voltage varying with time and place, and for low-voltage supplies it is 0.95. Lower voltage means lower fault current, so using 230 V on its own would fool you. We design to the worst case.

BS 7671 · Cmin explained · Reg 411.4.4 · p.73

Working

PEFC = (230 × 0.95) ÷ 0.397
     = 218.5 ÷ 0.397
     = 550.4 A   (0.55 kA)

Ia: the current for instant disconnection

Now the question is: can the 6 mm² CPC carry 550 A until the device trips? Think of it as a seat belt. It's tested well beyond the 70 mph limit, because it must hold even when something goes wrong. The CPC must outlast the protective device, so the device has to trip first.

Ia is the minimum current that makes the device operate instantaneously, which for a circuit-breaker means its fastest trip. The Appendix 3 pages ("the graphs of many nightmares") each have a table beside the graph. Read the table, not the curves.

Working

Fig 3A4 (Type B), 32 A → Ia = 160 A, trips in 0.1 s
PEFC 550.4 A exceeds Ia 160 A
→ the device will operate within 0.1 s during an earth fault
   (we need 0.4 s, so this is even better)
10 000 s100 s1 s0.4 s0.1 s time In 32 A: never trips I2 = 1.45 × In = 46.4 A trips only after a long time 0.4 s limit (Table 41.1) Ia = 5 × In = 160 A trips in 0.1 s PEFC 550 A well past Ia 3246.4160550 current (A), not to scale
A sketch (not to scale) of how to read a Type B curve for a 32 A device. The top of the Appendix 3 graphs is the long-time end (where I2 lives). The bottom is the instantaneous region (Ia).

The graph agrees with the table: follow the 32 A curve down to the bottom and it lands at about 160 A. (About 46.4 A sits at the top of the 32 A line, which is the I2 from step 9.)

BS 7671 · Appendix 3 · Fig 3A4 · Type B circuit-breakers (table of Ia beside the graph) · p.445

Don't forget the RCD in the RCBO. We've ignored it in the calculation (it's there because the regs demand it), so the circuit is even safer than the numbers show.

Test yourself on it

The tests are in the members’ area. Get one wrong and it shows you why, and where to revise.

Get access

Get new notes and exam tips from Sparky

About one email a fortnight. Unsubscribe any time. Privacy notice

That was one section. There are 583.

Sparky Study Notes is the whole Level 3 syllabus written up like this: the explanation, the worked example, and where it is in your book. With a video lesson for every part and a practice paper for every exam.

  • 583sections of written notes
  • 35video lessons
  • 1,463practice questions
  • 146diagrams, redrawn
  • 18th Edition
  • Building Regs
  • PAT
  • Fundamental Inspection & Testing
  • Initial Verification
  • Periodic Inspection & Testing
Get access — £100 12 months. One payment. See what’s inside