The type letter tells you the multiple of rating needed to trip it magnetically, and it is chosen for the load:
| Type | Trips instantly at | Where it belongs |
|---|---|---|
| B | 3–5 × In | Domestic — most of what you will meet |
| C | 5–10 × In | Loads with a higher switch-on surge, such as motors |
| D | 10–20 × In | Very high switch-on surges: transformers, X-ray machines, welding equipment |
✋Type D is not a cure for nuisance tripping. It needs far more fault current to trip instantly, so its maximum Zs is much lower and much harder to meet. Choose it for the load, and check the loop impedance will still give the disconnection time.
Where the types are listed. On-Site Guide · Table 7.2.7(ii) · p.102.
✋Changing the type changes your maximum Zs. Table 41.3 has a row per type. A question that says Type C and is answered from the Type B row is simply wrong.
Free section from Sparky Study Notes. The full Level 3 notes, 1,463 practice questions and the video lessons: sparkystudynotes.co.uk
Test yourself on it
The tests are in the members’ area. Get one wrong and it shows you why, and where to revise.
Get new notes and exam tips from Sparky
About one email a fortnight. Unsubscribe any time. Privacy noticeThat was one section. There are 583.
Sparky Study Notes is the whole Level 3 syllabus written up like this: the explanation, the worked example, and where it is in your book. With a video lesson for every part and a practice paper for every exam.
- 583sections of written notes
- 35video lessons
- 1,463practice questions
- 146diagrams, redrawn
- 18th Edition
- Building Regs
- PAT
- Fundamental Inspection & Testing
- Initial Verification
- Periodic Inspection & Testing