Before anything comes off: main switch off, isolated, locked off. You are about to disconnect green-and-yellow, and if there were a fault while it was off, extraneous parts could become live.

Then there are two tests, not one:

TestWhat it proves
End to end of the conductor itselfThe bonding conductor is continuous — this is your r2
That end to the pipeThe BS 951 clamp is genuinely in contact with the pipe
The two readings should be low and close together — a jump between them points to the clamp

Take the higher of the two as your value — it is not written on the schedule (see below).

On the schedule it is a tick, not a number. "Continuity and connection verified" is a tick box. You do not write a figure in for bonding — you just satisfy yourself that both readings are low and close together. Do it for every bonding conductor: water, gas, oil, structural steel.

Test yourself on it

The tests are in the members’ area. Get one wrong and it shows you why, and where to revise.

Get access

Get new notes and exam tips from Sparky

About one email a fortnight. Unsubscribe any time. Privacy notice

That was one section. There are 583.

Sparky Study Notes is the whole Level 3 syllabus written up like this: the explanation, the worked example, and where it is in your book. With a video lesson for every part and a practice paper for every exam.

  • 583sections of written notes
  • 35video lessons
  • 1,463practice questions
  • 146diagrams, redrawn
  • 18th Edition
  • Building Regs
  • PAT
  • Fundamental Inspection & Testing
  • Initial Verification
  • Periodic Inspection & Testing
Get access — £100 12 months. One payment. See what’s inside