Bonding continuity: a tick, not a numberIs 0.05 ohms the pass mark for bonding?
Free from the notes: Sparky’s video on it, the section word for word as members see it, and a PDF to keep.
The notes
Exactly as they are on the site.
There is no single target number. A bonding conductor’s resistance depends on its length and its cross-sectional area, nothing else. So work out what it should read: Table B1 gives milliohms per metre, and you need the length from the installer or the designer.
Example: an expected reading
10 mm² bonding conductor · 30 m Table B1 · 10 mm² = 1.83 mΩ/m R = (1.83 × 30) ÷ 1000 = 0.055 Ω
You don’t record a number for bonding. On EIC page 2, under main protective bonding conductors, give the material and size and tick “connection / continuity verified”. The condition report has the same box.
Guidance Note 3 · Appendix B · Table B1
Free section from Sparky Study Notes. The full Level 3 notes, 1,463 practice questions and the video lessons: sparkystudynotes.co.uk
Test yourself on it
The tests are in the members’ area. Get one wrong and it shows you why, and where to revise.
Get new notes and exam tips from Sparky
About one email a fortnight. Unsubscribe any time. Privacy noticeThat was one section. There are 583.
Sparky Study Notes is the whole Level 3 syllabus written up like this: the explanation, the worked example, and where it is in your book. With a video lesson for every part and a practice paper for every exam.
- 583sections of written notes
- 35video lessons
- 1,463practice questions
- 146diagrams, redrawn
- 18th Edition
- Building Regs
- PAT
- Fundamental Inspection & Testing
- Initial Verification
- Periodic Inspection & Testing