Before you isolate: the step most people were never taughtWhy clamp the earthing conductor before you touch anything?

Free from the notes: Sparky’s video on it, the section word for word as members see it, and a PDF to keep.

From Sparky’s full video lesson. Members get the whole lesson on every notes page.

The question at the end: Why clamp the earthing conductor before you touch anything? The answer is in the notes below.

The notes

Exactly as they are on the site.

Download these notesPDF · free to keep

Safe isolation used to begin at the main switch. It does not any more. An extra layer was added, and it sits in front of everything in the next section: you check whether current is flowing where it should not be, before you touch anything.

What you are looking for is neutral current diversion — current that has lost its proper route home and is finding another one. It happens when the combined protective-earth-and-neutral conductor in the supply network breaks on a PME supply. The neutral current then returns through whatever else is connected: the earthing system, the bonding, the pipework, the lot.

✋It is not only a TN-C-S problem. A TN-S or TT installation that shares extraneous-conductive-parts with a nearby PME installation can carry the same diverted current. And because it can originate next door, it can be present even when your installation is isolated. That is the whole reason this check exists.

With an open PEN, the line-to-neutral voltage can rise to around 400 V, and anything bonded to the earthing system — taps, a metal sink, the case of an appliance — can become live to touch.

Step 1 — clamp the earthing conductor and the main bonding, with the installation still on

A clamp meter round the earthing conductor, then round each main protective bonding conductor. In a dwelling with a maximum demand up to 100 A you would expect a few milliamps. A small reading is normal. A large one is the warning.

There is no published threshold, and that is deliberate. The book gives you an expectation, not a limit. You are being asked to judge. Worth knowing: an ordinary load clamp gets unreliable right where it matters — a leakage clamp is the accurate one below 5 mA.
✋If you suspect a broken PEN or diverted neutral current, ring the DNO immediately on 105. That is the action, not a note for later. It is a network fault and it is not yours to fix.

Guidance Note 3 · Appendix D · the eight steps in full

Test yourself on it

The tests are in the members’ area. Get one wrong and it shows you why, and where to revise.

Get access

Get new notes and exam tips from Sparky

About one email a fortnight. Unsubscribe any time. Privacy notice

That was one section. There are 583.

Sparky Study Notes is the whole Level 3 syllabus written up like this: the explanation, the worked example, and where it is in your book. With a video lesson for every part and a practice paper for every exam.

  • 583sections of written notes
  • 35video lessons
  • 1,463practice questions
  • 146diagrams, redrawn
  • 18th Edition
  • Building Regs
  • PAT
  • Fundamental Inspection & Testing
  • Initial Verification
  • Periodic Inspection & Testing
Get access — £100 12 months. One payment. See what’s inside