Bathrooms and special locationsWhat's allowed in bathroom zone 1?

Free from the notes: Sparky’s video on it, the section word for word as members see it, and a PDF to keep.

From Sparky’s full video lesson. Members get the whole lesson on every notes page.

The notes

Exactly as they are on the site.

Download these notesPDF · free to keep

A room containing a bath or shower is a special location. That includes a bedroom with a shower enclosure in it. An en-suite is its own room, but it's still a special location. We define zones because the closer you are to water, the higher the shock risk.

Zone 0 Zone 1 Zone 2 2.25 m 0.6 m ≥ 2.5 m socket outside zones
  • Zone 0: inside the bath or shower tray.
  • Zone 1: above the bath or tray up to 2.25 m from the floor (or to the shower head if higher).
  • Zone 2: 0.6 m out from the edge of zone 1.
  • Under the bath: zone 1 if you can reach it without a tool (no panel, or a panel that comes off by hand). If it takes a tool, such as unscrewing the panel or cutting sealed silicone, it is outside the zones. It is never zone 0.
  • Walk-in / wet room with no tray: zone 1 only, extending 1.2 m from the fixed water outlet. There's no zone 2.
  • All circuits in the location need 30 mA RCD protection (RCD or RCBO).
  • Sockets (other than shaver units) are allowed only at least 2.5 m horizontally from the boundary of zone 1.
  • Shaver supply units (BS EN 61558-2-5) are allowed in zone 2 and outside the zones, where direct spray from the shower is unlikely.
  • Plate switches go outside the zones, at least 0.6 m from the edge of the bath or shower, and must suit the location. Cord-operated switches are the exception: the cord is allowed into zones 1 and 2.
  • Equipment you'll see: a pull-cord switch (on the ceiling above 2.25 m, so the cord can hang into a zone), ceiling lights, a shaver socket, extractor fans, and an electric shower.
  • Where does the shower go? On the wall in zone 1, never in zone 0. Fixed equipment in zone 1 needs at least IPX4, or IPX5 if it will be cleaned with water jets. Allowed fixed equipment in zone 1 includes whirlpool units, electric showers and shower pumps, ventilation, towel rails, luminaires and water heaters.
  • Shaver socket: it has a safety isolating transformer inside, with a laminated core to reduce eddy-current losses. Because the output is isolated from earth, touching one conductor won't give an earth-path shock.
Common mistake
A shaver socket does not step down to 12 V. A standard shaver supply unit (BS EN 61558-2-5) actually gives an isolated 115 V / 230 V output. It's safe because it's isolated, not because it's low voltage. The 240 V marked on some of them is just the old nominal voltage.

Electrician's Guide to the Building Regs · 5.3 · locations containing a bath or shower: sockets, shaver units, plate switches, luminaires, showers and fans by zone · p.86 Electrician's Guide to the Building Regs · walk-in shower / wet room figure · p.89 Electrician's Guide to the Building Regs · table: minimum IP rating and equipment allowed per zone · p.87

On-Site Guide · Section 8 · zone requirements table (IPX4, IPX5 where water jets used for cleaning) · p.118 BS 7671 · Section 701 locations containing a bath or shower, zones in Regs 701.32.2–4 · from p.257 BS 7671 · Reg 701.32.3: the space under the bath is zone 1, or outside the zones if only accessible with a tool

Test yourself on it

The tests are in the members’ area. Get one wrong and it shows you why, and where to revise.

Get access

Get new notes and exam tips from Sparky

About one email a fortnight. Unsubscribe any time. Privacy notice

That was one section. There are 583.

Sparky Study Notes is the whole Level 3 syllabus written up like this: the explanation, the worked example, and where it is in your book. With a video lesson for every part and a practice paper for every exam.