Automatic disconnection of supply (ADS)

An electric shock from equipment happens when an exposed conductive part becomes live because of a fault. For example, a pan of water boils over into an oven and makes a connection between line and the metal case.

Four recognised protective measures against electric shock
  1. Automatic disconnection of supply (ADS): used almost universally in the UK.
  2. Double or reinforced insulation (Class II equipment): two layers of insulation, or one layer of reinforced insulation, so the outer casing can't become live.
  3. Extra-low voltage (SELV and PELV): for example SELV, supplied from a separated extra-low voltage (safety isolating) transformer.
  4. Electrical separation: supply from a separating transformer, like a shaver socket.
ADS is often used alongside one of the others. For example, a Class II light can still be on a circuit that uses ADS.

BS 7671 · Chapter 41 · protective measures generally permitted

ADS only works when the exposed conductive part is connected to the MET by a CPC, and the MET is connected back to the star point. You can't have ADS without that physical path. The circuit breakers, fuses and RCDs in the consumer unit need a path of low impedance. A low impedance means a high fault current, and a high fault current trips the device quickly.

Our example: fault current

Earth fault loop path = 1 Ω,  voltage = 230 V
I = V ÷ R = 230 ÷ 1 = 230 A of fault current
→ any circuit breaker or fuse in the consumer unit trips = ADS
(An RCD or RCBO works slightly differently, but it still needs an earth fault loop path.)

While the fault is there, the equipment is live until the device disconnects. That might be as quick as 0.1 s, or as long as 5 s. Different circuits have different maximum disconnection times, which is the subject of another masterclass.

How the shock happens

During that short window, imagine someone is touching the live exposed part with one hand and a metal pipe with the other. The pipe goes into the ground, so it's at earth potential (0 V). You can prove that: stand barefoot on your lawn and you're touching earth, but you feel nothing, because the ground is at 0 V.

The exposed part is at 230 V and the pipe is at 0 V, so there's a 230 V potential difference. The person bridges the gap. Current flows through their arms, across the chest and heart, and into earth through the extraneous conductive part.

✗ NOT bondedexposed part(faulty oven)pipeMET230 V0 V230 V ÷ 1000 Ω = 0.23 A through the chest✓ Main bonding (MPBC) fittedexposed part(faulty oven)pipeMETMPBCsamepotentialno potential difference → no current → no shock
Left: the person is the only path between 230 V and 0 V. Right: a main protective bonding conductor puts the pipe at the same potential as everything connected to the MET, so there's no potential difference across the person.

Dry hands

Average body resistance ≈ 1000 Ω
I = V ÷ R = 230 ÷ 1000 = 0.23 A
→ more than enough to send the heart into
  fibrillation (cardiac arrest)

Wet hands

Body resistance lower, say 500 Ω
I = V ÷ R = 230 ÷ 500 = 0.46 A
→ double the current. A child's resistance
  is lower still (thinner skin, smaller body).
A handy shorthand
People often say "voltage moves" or "voltage flows". Strictly, voltage is the potential difference that drives current, and it's the current through the body that does the harm. This chain is worth learning: no potential difference → no current → no electric shock.

Test yourself on it

The tests are in the members’ area. Get one wrong and it shows you why, and where to revise.

Get access

Get new notes and exam tips from Sparky

About one email a fortnight. Unsubscribe any time. Privacy notice

That was one section. There are 583.

Sparky Study Notes is the whole Level 3 syllabus written up like this: the explanation, the worked example, and where it is in your book. With a video lesson for every part and a practice paper for every exam.

  • 583sections of written notes
  • 35video lessons
  • 1,463practice questions
  • 146diagrams, redrawn
  • 18th Edition
  • Building Regs
  • PAT
  • Fundamental Inspection & Testing
  • Initial Verification
  • Periodic Inspection & Testing
Get access — £100 12 months. One payment. See what’s inside