Approved Documents A, B, C, E, F, L, MHow deep can you chase a wall?
Free from the notes: Sparky’s video on it, the section word for word as members see it, and a PDF to keep.
The notes
Exactly as they are on the site.
Worth doing: writing your own summary of every Approved Document. It's good exam prep.
A: Structure (notches, holes and chases)
Electrician's Guide to the Building Regs · 10.1.1 Notches and holes in joists (table and figure) · p.166 Electrician's Guide to the Building Regs · 10.1.2 Chases in walls · p.167 On-Site Guide · 7.3.1 cables through joists at least 50 mm from the top or bottom (or protected, 522.6.204) · p.102 On-Site Guide · Figure 7.3.1 Cables through joists · p.103 On-Site Guide · 7.3.2 and Table 7.3.2 cables in walls · p.104
B: Fire safety
Fire barriers where cables pass through walls and floors, and smoke and heat alarm positions (including loft conversions). Smoke and heat alarm questions do come up in the Building Regs exam.
Electrician's Guide to the Building Regs · Part B, fire safety and smoke/heat alarms · from p.168
C · E · F · L
- C: site preparation and resistance to contaminants and moisture. Stop gas and water getting in where cables enter.
- E: resistance to the passage of sound. Cables running through sound insulation have a reduced current-carrying capacity. Take care with recessed downlights in ceilings that contain sound insulation.
- F: ventilation.
- L1: conservation of fuel and power in dwellings. Energy-efficient lighting and automatic control of outside lights.
M: Access to and use of buildings
- When rewiring or altering an existing circuit, you don't have to meet Part M. The finished installation just has to be no less accessible than it was before.
- When refurbishing or rewiring, it's fine to mount switches and sockets in keeping with the existing property.
Electrician's Guide to the Building Regs · Approved Document M: switch and socket heights figure · p.186 Highlight or tab this image
P: Permitted cable routes
Cables hidden in walls must run in the permitted zones: horizontally or vertically in line with an accessory, or near the wall's edges and corners. If a cable runs outside the zones, e.g. diagonally between two outlets, and is less than 50 mm deep, it needs an earthed metal covering, earthed conduit or trunking, or mechanical protection against nails and screws. RCD protection is not a substitute for the zones. Capping over cables in a chase is common, but it's extra mechanical protection rather than a requirement.
Electrician's Guide to the Building Regs · Permitted cable routes / zones figure (blue = OK, orange = needs extra protection) · p.43 On-Site Guide · Similar permitted-zones figure
Free section from Sparky Study Notes. The full Level 3 notes, 1,463 practice questions and the video lessons: sparkystudynotes.co.uk
Test yourself on it
The tests are in the members’ area. Get one wrong and it shows you why, and where to revise.
Get new notes and exam tips from Sparky
About one email a fortnight. Unsubscribe any time. Privacy noticeThat was one section. There are 583.
Sparky Study Notes is the whole Level 3 syllabus written up like this: the explanation, the worked example, and where it is in your book. With a video lesson for every part and a practice paper for every exam.
- 583sections of written notes
- 35video lessons
- 1,463practice questions
- 146diagrams, redrawn
- 18th Edition
- Building Regs
- PAT
- Fundamental Inspection & Testing
- Initial Verification
- Periodic Inspection & Testing