Guidance Note 3 · p.134. Your instrument drifts over the years, and an instrument reading wrong is worse than no instrument at all. Two ways to stay on top of it:
| What it is | Rough cost | |
|---|---|---|
| Calibration | Sent to the manufacturer, returned with a certificate of calibration saying it reads within guidelines. Yearly, or every couple of years. | £50–100 |
| Accuracy log | Your own record — a spreadsheet will do — of checking the instrument yourself against known values between calibrations. | Your time |
The check itself is straightforward. Put your leads on a source you know the value of and see whether the meter agrees:
Checking against known values
Known 1 MΩ source -> insulation test should read 1 MΩ Known 10 MΩ source -> insulation test should read 10 MΩ Known 0.25 Ω -> continuity should read 0.25 Ω Acceptable drift = up to 5%, and you would hope for 1–2% A 10 MΩ source reading 7 MΩ -> way past 5%. The instrument is out.
Free section from Sparky Study Notes. The full Level 3 notes, 1,463 practice questions and the video lessons: sparkystudynotes.co.uk
Test yourself on it
The tests are in the members’ area. Get one wrong and it shows you why, and where to revise.
Get new notes and exam tips from Sparky
About one email a fortnight. Unsubscribe any time. Privacy noticeThat was one section. There are 583.
Sparky Study Notes is the whole Level 3 syllabus written up like this: the explanation, the worked example, and where it is in your book. With a video lesson for every part and a practice paper for every exam.
- 583sections of written notes
- 35video lessons
- 1,463practice questions
- 146diagrams, redrawn
- 18th Edition
- Building Regs
- PAT
- Fundamental Inspection & Testing
- Initial Verification
- Periodic Inspection & Testing