A 15 kW cooker, worked through34.57 amps on a 32 amp breaker?
Free from the notes: Sparky’s video on it, the section word for word as members see it, and a PDF to keep.
The notes
Exactly as they are on the site.
Same method, bigger appliance. 15,000 ÷ 230 = 65.22 A.
| Read correctly — Table A1 or A2 | Misread — 30% of the whole full load | |
|---|---|---|
| Load in excess of 10 A | 55.22 A | ignored |
| 30% of … | 55.22 × 0.3 = 16.57 | 65.22 × 0.3 = 19.57 |
| + 10 + 5 | 31.57 A | 34.57 A |
| Breaker | 32 A | 40 A — a size you did not need |
✋Both tables agree once they are read properly. Read correctly, 31.57 A sits under a 32 A device; misread, 34.57 A pushes you to 40 A for no reason.
Design high. A client who has a 5 kW cooker today will buy a 9 kW one in five years and will not mention it. Most installers fit a 32 A breaker on a domestic cooker circuit for exactly that reason, and the design allows for it.
Free section from Sparky Study Notes. The full Level 3 notes, 1,463 practice questions and the video lessons: sparkystudynotes.co.uk
Test yourself on it
The tests are in the members’ area. Get one wrong and it shows you why, and where to revise.
Get new notes and exam tips from Sparky
About one email a fortnight. Unsubscribe any time. Privacy noticeThat was one section. There are 583.
Sparky Study Notes is the whole Level 3 syllabus written up like this: the explanation, the worked example, and where it is in your book. With a video lesson for every part and a practice paper for every exam.
- 583sections of written notes
- 35video lessons
- 1,463practice questions
- 146diagrams, redrawn
- 18th Edition
- Building Regs
- PAT
- Fundamental Inspection & Testing
- Initial Verification
- Periodic Inspection & Testing