← All modules Core Electrics · Module 2 · Day 1 · 16/09/2026

Earthing, Bonding & Circuit Design

Study notes from the Module 2 Day 1 webinars. The morning covers earthing and bonding: exposed vs extraneous conductive parts, main and supplementary bonding, conductor sizes, touch voltage and cable colours. The afternoon covers design: cable types, installation reference methods, safe zones, socket circuits and the step-by-step cable selection method with a worked example.

Download PDF
Book reference page numbers appear in highlighted tags like this. "New" = current orange / green-orange editions. "Old" = previous brown / green-brown editions. Page numbers are as the tutor gave them on screen. Tab them in your books, but remember you can't write in them.
AM

Earthing & bonding

01Recap: earthing systems and Ze

SystemKey pointMax Ze
TN-C-S (PME)Neutral and earth combined in the supply (the PEN conductor, protective earth neutral), separated at the cut-out0.35 Ω
TN-SEarth and neutral separate the whole way, with the earth via the cable sheath0.8 Ω
TTEarth electrode, provided and paid for by the client. Ze is high because of ground conditions: a metal rod in the general mass of earth. Above 200 Ω the earth connection becomes unstable.21–200 Ω

Ze only measures the external earth path, from the transformer to the incoming MET or consumer unit. Under a fault the circuit breaker should trip in 0.4 s and a 30 mA RCD in 300 ms.

The tutor said about 40 minutes at the start of yesterday's (Day 2) afternoon recording was missed, which matches the note on that page. Older recordings of the mains position are available on the portal.

02Exposed vs extraneous conductive parts

Exposed conductive part
A metal part of the electrical installation that you installed and that someone can touch. It isn't normally live, but could become live under a fault.
Examples: metal conduit, a metal-clad socket or switch, a metal consumer unit, a metal shower case, a metal light fitting.
Extraneous conductive part
Metalwork that is not part of the electrical installation (you didn't install it) and that comes into the building from the ground, so it can introduce earth potential.
Examples: metal water and gas pipes, oil pipes, central heating and air-conditioning pipework, exposed metal structural parts (beams, steel studs), lightning protection.

Rule of thumb from the tutor: metal and you installed it means exposed. Metal and you didn't install it (it comes in from outside) means extraneous. If it's plastic it isn't conductive, so it's neither.

BS 7671 · Part 2 Definitions · "Extraneous-conductive-part" and "Exposed-conductive-part" Highlight both definitions. They're also in the Electrician's Guide and the On-Site Guide.

Myth: radiators don't automatically need bonding. They aren't something you install, and they don't come in from the ground. An electric towel rail is different: it's part of the installation, so it's an exposed conductive part.

03Main protective bonding

ground (general mass of earth) Service head (supply earth) Consumer unit earth bar CPCs → final circuits MET main earthing terminal earthing conductor 16 mm² earthingconductor metal water pipe clamp nearstopcock / entry gas meter clamp ≤ 600 mm from meter outlet main protective bonding conductors (10 mm²), each with a BS 951 clamp and label
Main protective bonding connects every extraneous conductive part to the MET. If there's no separate external MET, the earth bar in the consumer unit acts as the MET, and all the bonding, the earthing conductor and the CPCs go there.
BS 951 clamp colour (as taught)Environment
Red / silverInternal, dry areas
BlueExternal or slightly damp areas
GreenCorrosive or hazardous areas

Electrician's Guide to the Building Regs · 3.3.2 Earthing conductor and main protective bonding conductors: list of services to bond · p.58 new · p.52 old

Electrician's Guide to the Building Regs · Plastic supply pipes: no bonding needed. Bonding within 600 mm of meter or entry · p.59 new · p.52–53 old Electrician's Guide to the Building Regs · BS 951 earth clamp label image · p.63 new · p.57 old

On-Site Guide · Section 4 Bonding and earthing: earthing and main bonding figure · p.61

Read the notes under tables
The tutor said a lot of exam questions come from the small notes under tables and figures. Don't skip them.

04Sizing earthing and bonding conductors

CSA (cross-sectional area) is the size of the copper only, not including the insulation. A 10 mm² bonding conductor has 7 strands.

Quick rule for TN-S / TN-C-S (as taught): the earthing conductor is at least half the size of the supply tails, rounded up to the next available size. Main bonding is at least half the earthing conductor, rounded up with a minimum of 10 mm².
Example: 25 mm² tails → 25 ÷ 2 = 12.5 → 16 mm² earthing conductor → 16 ÷ 2 = 8 → 10 mm² main bonding
TN-C-S (PME) and TN-S
Supply line/neutral (mm²)Earthing conductor (mm²)Main bonding (mm²)
41010
61010
101010
161610
251610
351610
502516
703525
TT
Line conductor (mm²)Earthing conductor, not buried (mm²)Main bonding (mm²)
446
666
10106
161610
251610
351610
502516
703525

Values as shown on the session slides (highlighted rows = typical domestic). Always check the tables in your own book: Tables 3.3.2a and 3.3.2b. For TT, BS 7671 has extra conditions for buried earthing conductors.

Electrician's Guide to the Building Regs · Tables 3.3.2a and 3.3.2b: earthing and main protective bonding conductor sizes · p.59 new · p.53 old

05Why bond? Touch voltage and 1667 Ω

Write this down: the purpose of main protective bonding is to reduce the potential difference between exposed and extraneous conductive parts, so that no more than 50 V can pass from one to the other when an earth fault occurs.
✗ NOT bonded metal case FAULT: live exposed part metal pipe extraneous part fault current through YOU ✓ Bonded metal case FAULT: live bonding conductor same potential,fault takes this path

Current through a body

Body resistance ≈ 1000 Ω (less when wet)
I = V ÷ R = 230 ÷ 1000 = 0.23 A = 230 mA

About 50 mA (0.05 A) can stop your heart
(cardiac arrest). 230 mA is far more.
→ it's the CURRENT that kills.

Where 50 V touch voltage comes from

30 mA RCD → max 1667 Ω (BS 7671 Table 41.5)
V = I × R = 0.03 × 1667 = 50.01 V

So with a 30 mA RCD, keeping the resistance
of extraneous parts to earth ≤ 1667 Ω keeps
touch voltage at about 50 V.

A 30 mA RCD is set below the ~50 mA that can cause cardiac arrest. It gives additional protection by cutting off before serious harm.

BS 7671 · Table 41.5: max earth fault loop impedance for RCDs (30 mA → 1667 Ω) · p.77 new · p.70 old

06Supplementary bonding in bathrooms

Supplementary bonding links exposed and extraneous conductive parts locally, e.g. the metal pipes under a bath to a metal shower, so they stay at the same potential. You'll often see it as a loop of green/yellow between copper pipes, such as at a boiler. Somewhere along those pipes, a main bonding conductor goes back to the MET.

electric shower bath basin light electrictowel rail supplementary bonding (green/yellow) shower ↔ bath pipes ↔ basin pipes ↔ towel rail
The tutor called supplementary bonding a real pain to install, because every metal pipe connection needs linking. It's rarely installed now, because it can be left out when the three conditions below are met.
Supplementary bonding may be omitted in a room with a bath or shower (BS 7671 701.415.2) if all three are met:
  1. All final circuits in the location meet automatic disconnection of supply (ADS): a CB within 0.4 s, a 30 mA RCD within 300 ms.
  2. All final circuits in the location have additional protection by a 30 mA RCD.
  3. All extraneous conductive parts are effectively connected to the main protective bonding (back to the MET).

BS 7671 · Section 701: locations containing a bath or shower · Reg 701.415.2 supplementary bonding · p.257 new · p.242 old

Supplementary bonding conductor sizes

This depends on what you're linking and whether the conductor is mechanically protected, e.g. in conduit. A single-core green/yellow conductor has only one layer of insulation. The grey sheath on twin and earth is mechanical protection, and an RCD is additional protection, not mechanical.

Example from the session

Main protective bonding = 10 mm²
Link: electric shower (exposed part) → pipes under the bath (extraneous part)
Not mechanically protected → 6 mm² (still 6 mm² if protected)
Exposed part → exposed part, both mechanically protected with 10 mm² → 10 mm²

Electrician's Guide to the Building Regs · 3.3.3 Supplementary bonding conductors · Table 3.3.3 sizes · p.62 new · p.56 old

07Protective conductors and cable colours

Green/yellow = protective conductor. It's used only for:

  • the earthing conductor
  • main protective bonding conductors
  • supplementary bonding conductors
  • circuit protective conductors (CPCs)

The mix is 70% / 30% green and yellow, either way round. Never put green/yellow sleeving on a line or neutral.

ColourUse
Green/yellowProtective conductor
BlueNeutral
BrownLine (L1 on three-phase)
BlackLine 2 (three-phase)
GreyLine 3 (three-phase)

BS 7671 · Reg 514: identification of conductors · p.141 new · p.132 old Electrician's Guide to the Building Regs · Chapter 11: identification of conductors, old and new colours The tutor was asked about conductor ID in her own exam

PM

Electrical design

08What design means

Design isn't just picking any cable. It's based on the client's needs and on what's already there. Before adding or altering a circuit, check that the existing installation can:

Think of design as a chain. The load gives the design current, which decides the protective device, which with the installation method and conditions decides the cable size, which must then pass voltage drop. Example: if a client upgrades a shower from 5 kW to 8 kW, the existing cable may no longer be suitable.

BS 7671 · Appendix 1: British Standards and other standards referred to (about 22 pages) · p.411 new · p.385 old

09Cable types and marks of conformity

CableWhat it is / where it's used
Single coreOne insulated conductor, e.g. a 10 mm² green/yellow bonding conductor or a 16 mm² earthing conductor. "Single core" means one cable, not one strand.
Twin and earth (T&E)
flat, multicore, PVC/PVC, 70 °C
The standard domestic cable. 6242Y has a grey sheath. 6242B has a white sheath and is low smoke zero halogen (LSZH / LSF): less, lighter smoke in a fire, but harder to strip. Grey has a chalky powder inside so it strips easily, which is why most sparks prefer it.
FlexFlexible cable with many fine strands (e.g. 19), for appliances and pendants
MICCMineral insulated copper clad: copper sheath with magnesium oxide powder inside. Very tough and expensive, but moisture from sweaty hands or breath on the ends ruins it. White sheath = emergency lighting (e.g. listed buildings, schools, churches). Red sheath = fire alarms.
SWASteel wire armoured, with 3, 4 or 5 cores. Used commercially and industrially, and for outside sockets, lights and outbuildings. The armour can be used as the CPC. It's not the same as the DNO supply cable.

Marks of conformity show a product meets the required standards:

Electrician's Guide to the Building Regs · 2.2.2 Conformance to equipment standards: UKCA / UKNI marks · p.35 new · p.33 old

Messy doesn't mean non-compliant
One slide showed T&E draped loosely across loft joists with a single clip. It's ugly and poor workmanship, but it isn't against the rules, because it's clipped direct. A better job would drill through the joists (following Part A) or clip at every joist.

10Installation reference methods

The reference method describes how and where a cable is installed. This affects how much current it can carry, because heat has to escape. More insulation around a cable means more heat trapped, which means more resistance and a lower current rating. You may then need a bigger cable.

C clipped directto a surface best rating B conduit/trunkingon or in a wall,not insulated A in conduit ina thermallyinsulated wall Rule A vs B: the onlydifference is whetherthe wall is insulated. Mixed methods on onerun? Size for theworst case. 100 T&E on joist,insulation ≤100 mm 101 same, butinsulation >100 mm 102 stud wall, touchinginner wall surface 103 surrounded by insulation ≥0.5 m: half the rating
Simplified sketches. Methods 100–103 apply to flat twin and earth (thermoplastic, PVC/PVC, 70 °C). "Multicore flat cable" is another name for T&E. Method C (clipped direct) gives the highest current rating.

Electrician's Guide to the Building Regs · 2.3.1 Cable installation methods A, B, C · pp.38–39 new · pp.34–35 old Electrician's Guide to the Building Regs · Reference methods 100, 101, 102, 103 · Table 2.3.1 T&E current ratings · p.40 new · p.36 old

11Safe zones, depth and metal stud walls

✗ diagonal run: outside the zones socket switch 150 mm below ceiling 150 mmat corners Green = permitted zones: in line (vertically or horizontally) with an accessory, within 150 mm of the ceiling, or within 150 mm of a corner.

Cables concealed in a wall less than 50 mm deep must be protected in one of these ways:

  1. Enclosed in earthed metal conduit, trunking or ducting (or similar).
  2. Run in the permitted zones. This also needs 30 mA RCD additional protection.
  3. Part of a SELV/PELV circuit (extra-low voltage, covered later).

Electrician's Guide to the Building Regs · Permitted cable routes / safe zones figure and <50 mm depth rules · 2.3.2 Floors and ceilings · p.43 new

Metal stud walls: Reg 522.6.203
If a circuit is installed in a stud wall made mainly of metal, a 30 mA RCD is required, unless Reg 522.6.204 is followed. That means the cable has an earthed metallic covering, is in earthed conduit or trunking, has mechanical protection against penetration, or is part of SELV/PELV.
The RCD doesn't stop the cable being damaged. It protects the person from a shock if a screw or nail goes through it.

BS 7671 · Regs 522.6.202, 522.6.203, 522.6.204: cables in walls and metal stud partitions · p.152 new In the 18th Edition exam you find regs by number, not page. Practise.

Resistance, length and size
Resistance is directly proportional to length: double the length, double the resistance. It's inversely proportional to CSA: a bigger cable has lower resistance. Going from 4 mm² to 10 mm² (2.5× bigger) cuts resistance by 2.5×. Adding cable to a circuit raises its resistance, so test readings change.

12Socket circuits: rings and radials

Ring final circuit CU starts AND ends at the same CU terminals Radial circuit CU ends at the last point (e.g. cooker, shower, kitchen radial)
At each socket on a ring, the two lines share one terminal, as do the two neutrals and the two CPCs. It's parallel wiring, never series. Say "ring final circuit", not "ring main". A ring main is a distribution or supply circuit before the property. A spur is a branch off a ring or radial.
CircuitProtective deviceMin. copper CSA (T&E)Max. floor area
Ring final30 or 32 A2.5 mm²100 m²
Radial20 A2.5 mm²50 m²
Radial30 or 32 A4.0 mm²75 m²

Electrician's Guide to the Building Regs · 4.2 Final circuits using 13 A socket-outlets · Table 4.2.1 · p.77 new · p.72 old On-Site Guide · Appendix H · Table H2.1: final circuits using socket-outlets · p.218 new · p.210 old "Worth highlighting"

On-Site Guide · Appendix A: maximum demand

13Cable selection: the 7 steps

  1. Work out the design current, Ib. Ib = P ÷ V. Also note the installation reference method now, from the question.
  2. Select the protective device rating, In (e.g. B40), so that In ≥ Ib.
  3. Identify the installation method (C, B, A, 100–103…).
  4. Apply any correction factors, e.g. ambient temperature, grouping or thermal insulation.
  5. Calculate the tabulated current, It, that the cable must be able to carry.
  6. Select the cable size from the tables (BS 7671 or the On-Site Guide).
  7. Check the voltage drop.
Ib
Design current of the circuit: the load. "Ib", not "ID".
In
Nominal rating of the protective device in amps, e.g. the "6" on a B6.
Iz
Current-carrying capacity of the cable under normal conditions once correction factors have been applied. The Z here has nothing to do with impedance.
It
Tabulated current-carrying capacity: the value straight from the tables.
Ib ≤ In ≤ Iz
With no correction factors, Iz = It, so you pick a cable whose tabulated rating It ≥ In.

Voltage drop: radial circuits

VD = (mV/A/m × Ib × L) ÷ 1000

÷1000 because mV/A/m is in millivolts

Voltage drop: ring final circuits

VD = (mV/A/m × Ib × L) ÷ 4000

÷4000: the ring has 4 legs
(2 lines + 2 neutrals)
Max voltage dropSingle-phase 230 VThree-phase 400 V
Lighting: 3%6.9 V12 V
All other circuits (sockets, showers, cookers): 5%11.5 V20 V

If the voltage drop is too high, upsize the cable. You never downsize.

On-Site Guide · Appendix F: voltage drop explanation, radial formula (and ring formula, new edition only) · p.184 new · p.168 old Highlight the formula and the 3% / 5% paragraph

In real life
On most jobs a designer, your boss or the company has already done these calculations, and you install to the design. You still need to know the method for the exams and homework. The Level 4 design course takes it much further.

14Worked example: 8.5 kW shower

The question

An 8.5 kW electric shower is to be installed in a domestic property.
• Wired in PVC/PVC flat twin and earth
• Reference method 102
• Cable run 20 m
• Protective device: BS EN 60898 circuit breaker
• No rating factors
Select a suitable cable and protective device. Show all working.

Working

1) Design current
   Ib = P ÷ V = 8500 ÷ 230 = 36.96 A      (37 A is fine)

2) Protective device (domestic, so Type B)
   Next standard size ≥ 36.96 A → In = 40 A, Type B, BS EN 60898
   Check: Ib ≤ In → 36.96 ≤ 40 ✓

3–4) Method 102, no correction factors → Iz = It, and it must be ≥ In = 40 A

5–6) On-Site Guide Table F6 (70 °C flat T&E), method 102 column:
   6 mm²  → 35 A  ✗ (less than 40)
   10 mm² → 47 A  ✓  → select 10 mm² twin and earth

7) Voltage drop (not lighting, so max 5% = 11.5 V)
   Table F6, 10 mm² → 4.4 mV/A/m
   VD = (4.4 × 36.96 × 20) ÷ 1000 = 3.25 V
   3.25 V ≤ 11.5 V ✓

Answer: 10 mm² T&E on a 40 A Type B circuit breaker

On-Site Guide · Appendix B · Table B6: circuit-breaker ratings (BS EN 60898 / RCBOs) · p.159 new · p.145 old

On-Site Guide · Appendix F · Tables F4–F6: current-carrying capacity and voltage drop · from p.187 new · p.171 old On-Site Guide · Table F6: 70 °C thermoplastic flat twin and earth (It and mV/A/m) · p.193 new · p.177 old

Pick the right table
Table F4 is single-core cable and Table F5 is multicore round cable. Neither is T&E. Table F6 says flat thermoplastic sheathed cable, and that's the twin and earth table. It gives you both It and mV/A/m. The tutor said the design work is continued tomorrow morning.

15Calculator tips

16All book references from this day

Tab these pages. "New" = orange / green-orange editions, "old" = brown / green-brown.

BookWhatNewOld
Electrician's Guide to the Building Regs2.2.2 Marks of conformity (UKCA/UKNI)3533
Electrician's Guide to the Building Regs2.3.1 Installation methods A, B, C38–3934–35
Electrician's Guide to the Building RegsMethods 100–103, Table 2.3.1 T&E ratings4036
Electrician's Guide to the Building RegsSafe zones, <50 mm depth, 2.3.2 floors and ceilings43
Electrician's Guide to the Building Regs3.3.2 Main protective bonding: what to bond ★5852
Electrician's Guide to the Building RegsTables 3.3.2a/b earthing and bonding sizes; plastic pipes ★5953
Electrician's Guide to the Building RegsTable 3.3.3 supplementary bonding sizes ★6256
Electrician's Guide to the Building RegsBS 951 clamp label6357
Electrician's Guide to the Building RegsTable 4.2.1 socket circuits (ring/radial) ★7772
Electrician's Guide to the Building RegsChapter 11 identification of conductors
BS 7671Part 2 definitions: exposed and extraneous conductive parts ★
BS 7671Table 41.5: RCD max Zs (30 mA → 1667 Ω) ★7770
BS 7671Reg 514: identification of conductors ★141132
BS 7671Regs 522.6.202–204: cables in walls, metal stud walls152
BS 7671Section 701 bath/shower, Reg 701.415.2 supplementary bonding ★257242
BS 7671Appendix 1: British Standards list411385
On-Site GuideSection 4 bonding and earthing figure61
On-Site GuideAppendix B Table B6: circuit-breaker ratings159145
On-Site GuideAppendix F voltage drop formula (ring formula new only) ★184168
On-Site GuideAppendix F Tables F4–F6 start187171
On-Site GuideTable F6: flat T&E (It and mV/A/m) ★193177
On-Site GuideAppendix H Table H2.1: socket-outlet final circuits ★218210
On-Site GuideAppendix A: maximum demand

★ = the tutor specifically said to highlight it, or went through it in detail. Page numbers are as given in the session. Check them against your own copy.

17Self-test

Test yourself. Tap to reveal the answers.Answers are under each question.

A metal back box and metal socket front you installed: exposed or extraneous? A copper water pipe coming in from the ground?

Socket: exposed conductive part · water pipe: extraneous conductive part

What's the purpose of main protective bonding?

To reduce the potential difference between exposed and extraneous conductive parts, so no more than 50 V can pass from one to the other during an earth fault.

TN-C-S supply with 25 mm² tails. Earthing conductor and main bonding sizes?

16 mm² earthing conductor · 10 mm² main protective bonding

The incoming water service pipe is blue plastic all the way into the stopcock. Does it need main bonding?

No. There's no requirement to bond a plastic incoming service pipe.

Show where the 50 V touch voltage comes from for a 30 mA RCD.

V = I × R = 0.03 × 1667 = 50.01 V

Name the three conditions that let you leave out supplementary bonding in a bathroom.

All circuits meet ADS · all circuits have 30 mA RCD additional protection · all extraneous parts are connected to main protective bonding

Which four conductors may be green/yellow?

Earthing conductor · main protective bonding · supplementary bonding · CPC

What's the maximum floor area for a 20 A radial in 2.5 mm²? And a 32 A ring?

50 m² · 100 m²

A 7.2 kW shower on 230 V: Ib, and which Type B breaker?

Ib = 7200 ÷ 230 = 31.30 A → 32 A Type B

A 20 m radial carries 25 A in cable rated 7.3 mV/A/m. Voltage drop? OK for sockets? For lighting?

(7.3 × 25 × 20) ÷ 1000 = 3.65 V · sockets (≤11.5 V) ✓ · lighting (≤6.9 V) ✓

A ring final is 40 m long, Ib = 30 A, cable 18 mV/A/m. Voltage drop?

(18 × 30 × 40) ÷ 4000 = 5.4 V

What does Reg 522.6.203 require in a metal stud wall, and what does that RCD protect?

A 30 mA RCD (unless 522.6.204 is met). It protects the person from shock, not the cable from damage.

Unofficial student notes written from the Module 2 Day 1 webinar recordings (16/09/2026), shared free for fellow learners. Not produced or endorsed by the training provider. Bonding table values are as shown on the session slides. Always check against your course books, BS 7671 and your tutor. Spotted a mistake? Let us know so it can be fixed for everyone.

← All modules